This shows you the differences between two versions of the page.
Both sides previous revision Previous revision Next revision | Previous revision Next revision Both sides next revision | ||
cluster:112 [2013/05/14 14:30] hmeij [Overview] |
cluster:112 [2013/10/02 15:37] hmeij [Dell April-2013] |
||
---|---|---|---|
Line 22: | Line 22: | ||
- | * 2013 Dell measurements (see bottom table) put power consumption at 109, | + | |
+ | | ||
====== Details ====== | ====== Details ====== | ||
Line 148: | Line 150: | ||
| c35| 8| 13.69| | | c35| 8| 13.69| | ||
- | * Average for "still running" | + | * Average for "still running" |
+ | * (watts/ | ||
* In 2009 dollars that is $25,000 in power (plus that in cooling) or $50,000 per year | * In 2009 dollars that is $25,000 in power (plus that in cooling) or $50,000 per year | ||
* What is that in 2013 dollars (with cogen online in Pine Street)? | * What is that in 2013 dollars (with cogen online in Pine Street)? | ||
- | * | + | |
+ | Meeting with Peter 01Oct13 Summary | ||
+ | |||
+ | We have measured 19 nodes power consumption (pulling one unit out) with a Kill-A-Watt meter over 775+ hours to arrive at a mean consumption rate of 418.4 watts. That totals to 109,956 KwH/year in power consumption, | ||
+ | |||
+ | Based on 12.5 cents per Kwh (this is an all inclusive cost including natural gas cost, heat recoup costs, distribution, | ||
+ | |||
+ | If we could replace, or approximate, | ||