cluster:112 [2013/10/02 15:37] hmeij [Dell April-2013] |
cluster:112 [2013/10/02 15:42] hmeij [Dell April-2013] |
* What is that in 2013 dollars (with cogen online in Pine Street)? | * What is that in 2013 dollars (with cogen online in Pine Street)? |
| |
Meeting with Peter 01Oct13 Summary | We have measured 19 nodes power consumption (pulling one unit out) with a Kill-A-Watt meter over 775+ hours to arrive at a mean consumption rate of 418.4 watts. That totals to 109,956 KwH/year in power consumption ((watts/1000 Kw per hour) * 24 hours * 365 days * 30 servers), which is a low water mark as the racks in question also contain switches, two UPS units, and a disk array. (Note: Peter did a side calculation using the 4 watt measurement on panel directly and came up with 126,000 KwH/year which can be considered the high water mark estimate). |
| |
We have measured 19 nodes power consumption (pulling one unit out) with a Kill-A-Watt meter over 775+ hours to arrive at a mean consumption rate of 418.4 watts. That totals to 109,956 KwH/year in power consumption, which is a low water mark as the racks in question also contains switches, two UPS units, and a disk array. (Note: Peter did a side calculation using using the 4 watt measurement on panel and came up with 126,000 KwH/year which can be considered the high water mark estimate). | |
| |
Based on 12.5 cents per Kwh (this is an all inclusive cost including natural gas cost, heat recoup costs, distribution, maintenance etc) the hardware burns away $13,744.50 per year. Best guess is cooling costs are at least that (another possible low water mark) so the total cost for all power consumption is $27,489 per year. If we run the hardware for another 3 years that total cost is $82,467. | |
| |
If we could replace, or approximate, the 30 compute nodes' computational power (0.6 teraflops) and job slots (240) with new hardware that consumes 50% less in power, our ROI is 6 years. | Based on 12.5 cents per Kwh (this is an all inclusive cost including natural gas cost, heat recoup costs, distribution, maintenance etc) the hardware burns away $13,744.50 per year. Best guess is cooling costs are at least that (another possible low water mark) so the total cost for all power consumption is $27,489 per year. If we run the hardware for another 3 years that total cost is $82,467. |
| |
| |
| |
| If we could replace, or approximate, the 30 compute nodes' computational power (0.6 teraflops) and job slots (240 cores) with new hardware that consumes 50% less in power, our ROI is 6 years based on the low water mark numbers. |
| |
| |