Line 52: Line 52:
  
  
-^Tnodes^Tcores^THcores^Tmem gb^Watts^%of Dell^TEnergy^TEnergy $/Y^TEsavings $/Y^Quote $^ROI Y^Gflops^ + Tnodes^  Tcores^  THcores^  Tmem gb^  Watts^  %of Dell^  TEnergy^  TEnergy $/Y^  TEsavings $/Y^  Quote $^   ROI Y^  Gflops^ 
-|10|160|320|2,560|3,650|29|7,300|7,994|19,495|$76,866|3.9|3,328 | + 10|  160|  320|  2,560|  3,650|  29|  7,300|  7,994|  19,495|  76,866|  3.9|  3,328| 
-| 9|144|228|2,304|3,285|26|6,570|7,194|19,495|$76,866|3.9|3,328 + 9|  144|  288 2,304|  3,285|  26|  6,570|  7,194|  20,295 69,290 3.4 2,995
-| 8|128|256|2,048|2,920|23|5,840|6,395|19,495|$76,866|3.9|3,328 + 8|  128|  256|  2,048|  2,920|  23|  5,840|  6,395|  21,094 61,714 2.9|  2,662
-| 7|112|224|1,792|2,555|20|5,110|5,596|19,495|$76,866|3.9|3,328 |+ 7|  112|  224|  1,792|  2,555|  20|  5,110|  5,596|  21,893 54,138 2.4 2,329|
  
  
 +==== Summary ====
 +
 +The Dell racks were bought in 2006. They contain 30 compute nodes, two UPS units, two disks arrays and two switches. Measurements of 2/3rds of the compute nodes with a Kill-A-Watt meter yields an average consumption of 418.4 watts (if the nodes are computing or not).  That totals to 109,956 KwH/year for power, a low water mark. Measurements at the utility panel for one of the racks yields a consumption of 126,000 KwH/year. Cooling requirements (not measured) are assumed to be equal to that.
 +
 +Using the low water mark, and a cost per KwH (inclusive of cogen generation costs, maintenance, CP&L power imports, heat reclamation costs, etc), the total cost for both  power and cooling consumption is estimated at $27,489 per year for the Dell racks.
 +
 +New hardware could replace the Dell's functionality and reduce power/cooling needs in the data center while yielding significant savings.  An 8-node cluster with each node comprised of dual 8 core CPUs, each with 256 GB of memory and a 15K 300 GB hard disk, all nodes connected to a high throughput/low latency switch, would match or exceed key parameters such as gigaflops of computational power and number of job slots provided (with hyperthreading enabled).
 +
 +Such a cluster would consume 77% less energy generating $21,094 in saving per year (after accounting for energy needs of that 8-node cluster).  This implies that in 2.9 years the cost of acquiring that 8-node cluster ($61,714) will be recouped. Based on the low water mark.
  
 \\ \\