cluster:178 [2019/08/14 17:37] hmeij07 [July Photos] |
cluster:178 [2019/08/16 12:33] hmeij07 [Tech Summary] |
The HPCC is in the top row of racks on the left (room for 3 additional racks, light yellow dots, 5 existing racks, dark yellow dots). | The HPCC is in the top row of racks on the left (room for 3 additional racks, light yellow dots, 5 existing racks, dark yellow dots). |
| |
| ===== Tech Summary ===== |
| |
| You don't get approval for a roughly $250K project without some serious reasons and numbers. To start with an air flow dynamics analysis, and attempted improvements, utterly failed to improve our data center's environment. With the help of [[http://www.feace.com|FEACE]] we next embarked measuring our power consumption and cooling needs. The proposed solution is described above. The significant improvements are; abandon subfloor cold air delivery, reduce square footage cooled, free cooling below 45 degree ambient air, and much more energy efficient cooling units. |
===== June Meetings ===== | ===== June Meetings ===== |
| |
{{:cluster:pp_jul31_03_small.jpg?nolink&300|}} Drone rooftop top view\\ | {{:cluster:pp_jul31_03_small.jpg?nolink&300|}} Drone rooftop top view\\ |
{{:cluster:100_2343_small.jpg?nolink&300|}} Odd location for dim switch\\ | {{:cluster:100_2343_small.jpg?nolink&300|}} Odd location for dim switch\\ |
{{:cluster:100_2346_small.jpg?nolink&300|}} Novel use floor pedestal\\ | {{:cluster:100_2346_small.jpg?nolink&300|}} Novel use subfloor pedestal\\ |
{{:cluster:100_2347_small.jpg?nolink&300|}} Out of service foam fire suppressant\\ | {{:cluster:100_2347_small.jpg?nolink&300|}} Out of service foam fire suppressant\\ |
{{:cluster:100_2368_small.jpg?nolink&300|}} Do Not Operate, my life depends on it\\ | {{:cluster:100_2368_small.jpg?nolink&300|}} Do Not Operate, my life depends on it...\\ |
{{:cluster:100_2367_small.jpg?nolink&300|}} Transformer, new pipes, old mail tubes\\ | {{:cluster:100_2367_small.jpg?nolink&300|}} Transformer, new&old pipes, old mail tubes\\ |
{{:cluster:100_2358_small.jpg?nolink&300|}} Hot gas (left, arrives), cold liquid (right, returns)\\ | {{:cluster:100_2358_small.jpg?nolink&300|}} Hot gas (left, arrives), cold liquid (right, returns)\\ |
{{:cluster:100_2364_small.jpg?nolink&300|}} Hot gas in, cooled to Liquifier (black)\\ | {{:cluster:100_2364_small.jpg?nolink&300|}} Hot gas in, cooled to Liquifier (black)\\ |
{{:cluster:100_2352_small.jpg?nolink&300|}} From Liquifier to Economizer\\ | {{:cluster:100_2352_small.jpg?nolink&300|}} From Liquifier to Economizer\\ |
{{:cluster:100_2354_small.jpg?nolink&300|}} Charging, R-410A gas only, zeotropic mixture\\ | {{:cluster:100_2354_small.jpg?nolink&300|}} Charging, R-410A gas only, zeotropic mixture\\ |
| {{:cluster:100_2378_small.jpg?nolink&300|}} Seriously. Pink! Official industrial color\\ |
| {{:cluster:100_2369_small.jpg?nolink&300|}} New Hall/Atwater-Excley generator, 450 Kw, 16,000 lbs\\ |
| |
| |
\\ | \\ |