Line 20: Line 20:
  
 You don't get approval for a roughly $250K project without some serious reasons and numbers. To start with an air flow dynamics analysis, and attempted improvements, utterly failed to improve our data center's environment. With the help of [[http://www.feace.com|FEACE]] we next embarked measuring our power consumption and cooling needs. The proposed solution is described above.  The significant improvements are; abandon subfloor cold air delivery, reduce square footage cooled, free cooling below 45 degree ambient air, and much more energy efficient cooling units. You don't get approval for a roughly $250K project without some serious reasons and numbers. To start with an air flow dynamics analysis, and attempted improvements, utterly failed to improve our data center's environment. With the help of [[http://www.feace.com|FEACE]] we next embarked measuring our power consumption and cooling needs. The proposed solution is described above.  The significant improvements are; abandon subfloor cold air delivery, reduce square footage cooled, free cooling below 45 degree ambient air, and much more energy efficient cooling units.
 +
 +There are two sources of power and most racks (other than HPCC) are tied into both. Emergency power that comes from the enterprise UPS (with bypass to utility power and backed by gas generator) and plain utility power delivered directly from the power grid. The UPS logs kwh consumed. The utility panels were clamped for a month and consumption logged. The HPCC racks were individually logged using an PDU with amp meter. Since the HPCC is a big variable much effort was spend to assess it's consumption, read the [[cluster:176|HPC Power]] page.
 +
 +^  Excley Data Center Loads  ^  total kW  ^
 +|  Emergency power backed racks (x2)|  43.5|
 +|  HPC Racks|  22 (Peak)|
 +|  Storage (rstore)|  2|
 +|  GPU expansion|  7|
 +^  Sub Total^  74.5 kW^
 +|  Expansion Capacity - up to 25% of current load|  18|
 +^  Sub Total^  92.5 kW^
 +|  Lighting load and building envelope losses|  2|
 +^  Total Data Center Cooling Load^  94.5 kW^
 +|  Miscellaneous Load - UPS Lossess|  5|
 +
 +The total cooling load for the data center space including load values above, and a potential for a 25% capacity increase is approximately – 94.5 kW. The 5 kW load associated with heat loss from the UPS is not factored into the data center cooing load and is planned to be handled separately.
 +
 +It is recommended for the purpose of the study to use a total load of approximately 88kw, based
 +on the capacity of the proposed cooling units. That would account for enough capacity to handle
 +today's load and associated equipment losses with room to grow by approximately 18%. The
 +cooling installed would also have the ability to be expandable if additional growth is required
 +beyond the 88 kW design limit. The breakdown of the proposed load is as follows:
 +
 +^  Proposed Excley Data Center Loads  ^  total kW  ^
 +|  Emergency power backed racks (x2)|  43.5|
 +|  HPC Racks|  22 (Peak)|
 +|  Storage (rstore)|  2|
 +|  GPU expansion|  7|
 +^  Sub Total^  74.5 kW^
 +|  Expansion Capacity - up to 18% of current load|  13|
 +^  Sub Total^  87.5 kW^
 +|  Lighting load and building envelope losses|  2|
 +^  Total Data Center Cooling Load^  89.5 kW^
 +|  Miscellaneous Load - UPS Lossess|  5|
 +
 +
 +
 ===== June Meetings ===== ===== June Meetings =====
  
Line 150: Line 187:
  
 Cancelled Cancelled
 +
 +**8/20**
 +
 +Meetings moved to Thu afternoon (1pm now vs 7:30am)
 +New CRAC2 unit on, data center temp dropped 5-7 degrees
 +Modular wall up
 +Fire suppressant install next, followed by ceiling
 +Reconfigure floor tiles near CRAC2
 +Old CRAC1 demolishing started
 +
  