Rack Power
Rack | L6-30P | I Amps | P Amps | I Watts | P Watts | I KwH/Y | P KwH/Y | I $/Y | P $/Y |
R4R04 | 3 | 22 | 37 | 4,576 | 7,696 | 40,085 | 67,416 | 5,010 | 8,427 |
R4R05 | 4 | 17 | 34 | 3,536 | 7,072 | 30,975 | 61,950 | 3,872 | 7,743 |
R4R06 | 2 | 6 | | 1,204 | | 8,970 | | 1,121 | |
R4R07 | 2 | 14 | 34 | 2,912 | 7,072 | 25,509 | 61,950 | 3,189 | 7,744 |
R4R08 | 2 | 4 | | 832 | | 7,288 | | 911 | |
Total | 13 | 63 | 105 | 13,060 | 21,840 | 114,405 | 542,682 | 14,300 | 67,835 |
Metered
R4R04 rack: three L6-30P supplies
All dual power supply nodes
n33-n37 one gpu/node, 94/120 cpu jobs = 5 amps
n33-n37 above with 3 network switches 8 amps
m33-n37 need to get data all gpus working = 7 amps
n78 with 0 jobs = 0 amps, all gpus working = 2 amps
mindstore0 and ringtail = 1 amps
cottontail and shartptail (no rsyncs) = 1 amps
cottontail and shartpail (rsyncs) = ?? amps ←– DO
under modest load 8+2+1+1=12, observed 14 amps on left PDUs (front/back)
split n78 to right PDU (right side 2 amps plus all single power)
all storage 50% on UPS in R4R05, minuscule reduction
All single power supply nodes add to right PDU
n38-n41 idle load = 3 amps, so 6 amps for all nodes
n38-n41 full load = 7 amps, so 14 for all nodes
TOTAL IDLE load (14)+(6+2)= 22 amps
TOTAL PEAK load (14+7)+(14+2)= 37 amps …37/90 or 41%
R4R05 rack: four L6-30P supplies
R4R06 rack: two L6-30P supplies
R4R07 rack: two L6-30P supplies
All single power supplies
mw128 10 nodes, idle = 4 amps, for all nodes 8 amps
mw128 10 nodes, peak = 8 amps, for all nodes 16 amps
two switches = 2 amps
tinymem 7 nodes, idle = 2 amps, for all nodes 4 amps
tinymem 7 nodes, peak = 8 amps, for all nodes 16 amps (DOM,no hard disk)
TOTAL IDLE load 8+2+4= 14 amps
TOTAL PEAK load 16+2+16= 34 amps …34/60 is 51%
R4R08 rack: two L6-30P supplies
Mostly empty rack
All dual power supplies
TOTAL 4 amps