As part of our reevaluation of our data center cooling capacity and overhaul, we need to get a handle on non-emergency power consumption in data center. This will be done by a third party consultant by clamping power cables in the penthouse of Excley. So I bought myself a metered PDU and have been busy plugging entire racks into it one at a time. I then measure “idle” and “peak” amperage consumption. The end picture should reveal how much Kw the HPC consumes of all non-emergency power (that is not on enterprise UPS). And we'll figure out how much Physical Plant spends supporting the HPC. Thanks PP!

  • “Idle” means not very busy, most of the time something is happening (ie backups)
  • “Peak” means very busy, most queues entirely full.
  • Metered Amps * 208V = Watts
  • Watts * (24 * 365)/1000 = KwH/Y
  • kwH/Y * $0.12 = $/Y (mix cogen and utility, 2013 assumption by Pete of PP)
  • Double the $/Y to include cooling costs (Pete of PP assumption)
Idle Peak Idle Peak Idle Peak Idle Peak
Rack L6-30P Amps Amps Watts Watts KwH/Y KwH/Y $/Y $/Y
R4R04 3 22 37 4,576 7,696 40,085 67,416 5,010 8,427
R4R05 4 17 34 3,536 7,072 30,975 61,950 3,872 7,743
R4R06 2 6 1,204 8,970 1,121
R4R07 2 14 34 2,912 7,072 25,509 61,950 3,189 7,744
R4R08 2 4 832 7,288 911
Total 13 63 105 13,060 21,840 114,405 542,682 14,300 67,835
  • in 2013 we found for Dell Racks:

Metered

R4R04 rack: three L6-30P supplies

  • All dual power supply nodes
    • n33-n37 one gpu/node, 94/120 cpu jobs = 5 amps
    • n33-n37 above with 3 network switches 8 amps
    • m33-n37 need to get data all gpus working = 7 amps
    • n78 with 0 jobs = 0 amps, all gpus working = 2 amps
    • mindstore0 and ringtail = 1 amps
    • cottontail and shartptail (no rsyncs) = 1 amps
    • cottontail and shartpail (rsyncs) = ?? amps ←– DO
    • under modest load 8+2+1+1=12, observed 14 amps on left PDUs (front/back)
      • split n78 to right PDU (right side 2 amps plus all single power)
      • all storage 50% on UPS in R4R05, minuscule reduction
  • All single power supply nodes add to right PDU
    • n38-n41 idle load = 3 amps, so 6 amps for all nodes
    • n38-n41 full load = 7 amps, so 14 for all nodes
  • TOTAL IDLE load (14)+(6+2)= 22 amps
  • TOTAL PEAK load (14+7)+(14+2)= 37 amps …37/90 or 41%

R4R05 rack: four L6-30P supplies

  • All dual power supplies
    • greentail, sanscratch storage, idle = 2 amps
    • greentail, 1TB write to sanscratch = 2 amps
    • above + 3 switches, petal/swallow/cotton2 tails, hpcmon = 5 amps
    • n1-n32 (25 bodes), idle = 5 amps
    • gaussian jobs on n1-n32 = 12 amps
  • TOTAL IDLE load 2+5= 7 amps x2 = 17 amps
  • TOTAL PEAK load 5+12= 17 amps x 2 = 34 amps … 34/120 or 28%

R4R06 rack: two L6-30P supplies

  • Mostly empty rack
    • AC unit working = 8 amps (120V)
    • two switches = 2 amps (208V)
    • TOTAL 6 amps

R4R07 rack: two L6-30P supplies

  • All single power supplies
    • mw128 10 nodes, idle = 4 amps, for all nodes 8 amps
    • mw128 10 nodes, peak = 8 amps, for all nodes 16 amps
    • two switches = 2 amps
    • tinymem 7 nodes, idle = 2 amps, for all nodes 4 amps
    • tinymem 7 nodes, peak = 8 amps, for all nodes 16 amps (DOM,no hard disk)
  • TOTAL IDLE load 8+2+4= 14 amps
  • TOTAL PEAK load 16+2+16= 34 amps …34/60 is 51%

R4R08 rack: two L6-30P supplies

  • Mostly empty rack
  • All dual power supplies
    • ringtail, mindstoresrv1 storage = 2 amps
    • two switches = 2 amps
  • TOTAL 4 amps