cluster:176 [2018/11/20 19:18]
hmeij07 [HPC Power]
cluster:176 [2019/03/06 19:29] (current)
hmeij07 [Metered]
Line 14: Line 14:
   * Double the $/Y to include cooling costs (Pete of PP assumption)   * Double the $/Y to include cooling costs (Pete of PP assumption)
  
-^  HPC  ^^  Idle ^  Peak  ^  Idle  ^  Peak  ^  Idle  ^  Peak  ^  Idle  ^  Peak  ^ +^  HPC  ^^  Idle ^  Peak  ^  Idle  ^  Peak  ^  Idle  ^  Peak  ^  Idle  ^  Peak  ^    
-^  Rack  ^  L6-30P  ^  Amps ^  Amps  ^  Watts  ^  Watts  ^  KwH/Y  ^  KwH/Y  ^  $/Y  ^  $/Y  ^ +^  Rack  ^  L6-30P  ^  Amps ^  Amps  ^  Watts  ^  Watts  ^  KwH/Y  ^  KwH/Y  ^  $/Y  ^  $/Y   Note  ^ 
-|  R4R04  |  3  |  22  |  37  |  4,576  |  7,696  |  40,085  |  67,416  |  5,010  |  8,427  | +|  R4R04  |  3  |  22  |  37  |  4,576  |  7,696  |  40,085  |  67,416  |  5,010  |  8,427   "sharptail rack"  | 
-|  R4R05  |  4  |  17  |  34  |  3,536  |  7,072  |   30,975  |  61,950  |  3,872  |  7,743  | +|  R4R05  |  4  |  17  |  34  |  3,536  |  7,072  |   30,975  |  61,950  |  3,872  |  7,743   "greentail rack"  | 
-|  R4R06  |  2  |  6  |    |  1,204  |    |  8,970  |    |  1,121  |    | +|  R4R06  |  2  |  6  |    |  1,204  |    |  8,970  |    |  1,121  |    |  empty  
-|  R4R07  |  2  |  14  |  34  |  2,912  |  7,072  |  25,509  |  61,950  |  3,189  |  7,744  | +|  R4R07  |  2  |  14  |  34  |  2,912  |  7,072  |  25,509  |  61,950  |  3,189  |  7,744   "mw128/tinymem"  | 
-|  R4R08  |  2  |  4  |    |  832  |    |  7,288  |    |  911  |    | +|  R4R08  |  2  |  4  |    |  832  |    |  7,288  |    |  911  |    |  mostly empty  
-|  Total  |  13  |  63  |  105  |  13,060  |  21,840  |  114,405  |  191,318  |  14,300  |  23,915  |+|  Total  |  13  |  63  |  105  |  13,060  |  21,840  |  114,405  |  191,318  |  14,300  |  23,915  |    |
  
-In 2013 we found for our Dell Racks purchased in 2006 (full of PE1950 and PE2950 servers)+In 2013 we found for our Dell Racks purchased in 2006 (full of PE1950 and PE2950 servers) [[cluster:123|Replace Dell Racks]]
  
   * 115,000 KwH/Y per rack for power   * 115,000 KwH/Y per rack for power
Line 77: Line 77:
     * mw128 10 nodes, idle = 4 amps, for all nodes 8 amps     * mw128 10 nodes, idle = 4 amps, for all nodes 8 amps
     * mw128 10 nodes, peak = 8 amps, for all nodes 16 amps     * mw128 10 nodes, peak = 8 amps, for all nodes 16 amps
 +      * 11/28/2018 17 amps observed (with 6/18 nodes at load 36)
 +      * 03/05/2019 23 amps observed (...wengang jobs, mw128 nodes only! 23+16=39of60 possible)
     * two switches = 2 amps     * two switches = 2 amps
     * tinymem 7 nodes, idle = 2 amps, for all nodes 4 amps     * tinymem 7 nodes, idle = 2 amps, for all nodes 4 amps
cluster/176.1542741511.txt.gz · Last modified: 2018/11/20 19:18 by hmeij07